FISHER  Type HSR

FISHER Type HSR

Type HSR direct-operated, spring-loaded pressure reducing regulators provide control in residential, commercial, and industrial applications for natural, manufactured, or liquefied petroleum gases.Internal relief across the diaphragm helps minimize overpressure. Any outlet pressure over the start-to-discharge point of the nonadjustable relief valve spring moves the diaphragm off the relief valve seat, allowing excess pressure to vent.
Regulators meet ANSI B109.4/CGA 6.18.

Specifications

Body Size and End Connection Styles NPS 3/4 x 3/4, 3/4 x 1, 1 x 1, NPT All sizes available in Globe or Angle Body

Allowable Inlet Pressure Emergency: 150 psig / 10,3 bar

Maximum Operating Pressure: 125 psig / 8,6 bar

Allowable Outlet Pressure Emergency (Casing): 25 psig / 1,7 bar

Maximum Operating Pressure to Avoid Internal Parts Damage: 3 psi / 0,21 bar differential above outlet pressure setting

Outlet Pressure Ranges 4-inches w.c. to 2.2 psig / 10 mbar to 0,15 bar in 7 ranges

Pressure Registration Internal

Temperature Capabilities -20 to 160°F / -29 to 71°C

Features

Angle Bodies

Globe Bodies

High Capacity

Compact Design

High Capacity Internal Relief

Meets or Exceeds ANSI B109.4 / CGA 6.18 Requirements

Fixed Factor / PFM Accuracy